WYQ6 series of liquid resistance soft starter

首页 > en产品中心 > enMotor control center

WYQ6 series of liquid resistance soft starter

1. Direct Starting Problem
     Motor will create big current shake if start directly ( 5-8 times more than rated current), it makes big strike for electic grid and loaded equipment, heavily reduce motor and equipment service life,Sometimes motor burnt .so,stepless smooth start and stop is neccessory.
 2. Intelligent WYT Main Function
     (1). Smooth start, without shook to equipment, extend the using life,save equipment maintain cost.
     (2). Reduce start current, reduce  temperature increasing of motor, largely extend  the long of motor.
     (3). Full protect motor and loaded equipment.
 3. Range of application
     Suitable to heavy load soft starting of wound rotor asynchronous motor,
especially in industrial or mines with unstable or lower voltage.
 4. Unique feature
     (1). Low starting current: the starting current is<= 1.3Ie(A)
     (2). The cabinet and water tank adopt a full-closed structure, which can avoid evaporating of the electrolyte,lengthen the equipment working life and reduce the mantaining frequency.
     (3). It can start under a lower voltage, for example, start in 5.5KV when rated voltage 6KV.
     (4). With a cycle pump, a unique automatic cycle colling system designed for this product, can release the leat in the tank in very short time.
     (5).. Can started continuously for 5-10 times.
     (6). Adpts worm gear and worm lifter as the transformation tool, which is stable,reliable and noiseless.
     (7). The equipment has reliable cabinet struction, which is wholly automatically operated and convenient to be installed and maintained.
 
 5. Operating Principle

               For wound rotor asynchronous motor, when the grid voltage and frequency are invariant, the connection of the starting resistor  to the rotor loop will reduce the starting current and get a larger starting torque.      Putting special compound electrolyte into the rotor loop of the  controlled winding motor as the liquid resistance, when the stator receive the signal of the motor starting,  it will change the location of the electrolyte automatically, so as to reduce the resistance value gradually. when the resistance reached the minimum level, the sensor closed and motor rotor star connected directly, then the equipment start smoothly with a low current, large torque.

suitable motorAC wound rotor  motor
Rated voltage380V~ 10KV
Rated power75KW ~11000KW
Start currentless than motor rated current 1.5 times at least
continous start time5~10 times
cabinet sizemmTo demand
working condition   ( if special, pls clarify)temperature-40C ~ + 50C
air humidity<=90%
Altitduenormal 2000m



No.1, Wanzhou Road, Xiangyang City, Hubei,

Direct Sales:(86)710-3400567 3401338

Service Hotline:(86)0710-3405771